Strany 2 - Safety Precautions

- 1 -HWE09120 GBI Read Before Servicing[1] Read Before Servicing ...

Strany 3

[ VI Refrigerant Circuit ] - 91 -HWE09120 GB2. Indoor UnitPart Name Symbol (functions) Notes Usage Specification Check method Linear expan-sion valv

Strany 4

- 92 -[ VI Refrigerant Circuit ]GBHWE09120

Strany 5 - Before installing the unit

- 93 -HWE09120 GBVII Control[1] Functions and Factory Settings of the Dipswitches ... 95[2] Cont

Strany 6

- 94 -

Strany 7 - Before the test run

[ VII Control ] - 95 -HWE09120 GBVII Control[1] Functions and Factory Settings of the Dipswitches1. Outdoor unit(1) Control board1) Unless otherwis

Strany 8 - CONTENTS

[ VII Control ]- 96 -HWE09120 GB1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF fo

Strany 9

[ VII Control ] - 97 -HWE09120 GB1) Unless otherwise specified, leave the switch to OFF where indicated by "-," which may be set to OFF f

Strany 10 - Read Before Servicing

[ VII Control ]- 98 -HWE09120 GB(2) INV board1) PUHY-P72, P96, P120, P144YJMU-A, PUHY-P72TJMU-AFunctions are switched with the following connector

Strany 11

[ VII Control ] - 99 -HWE09120 GB2. Function of the switch (Indoor unit)(1) Dipswitches1) SW1,3(2) Address switchActual indoor unit address settin

Strany 12 - [1] Read Before Servicing

[ VII Control ]- 100 -HWE09120 GB3. Function of the switch <Remote controller>(1) MA remote controller (PAR-20MAU)The SW is located at the bot

Strany 14 - [3] Piping Materials

[ VII Control ] - 101 -HWE09120 GB(2) ME remote controller (PAR-F27MEA-US)Set the address of the remote controller with the rotary switch.To set add

Strany 15 - Dimension A

[ VII Control ]- 102 -HWE09120 GB[2] Controlling the Outdoor Unit-1- Outline of Control MethodThe outdoor units are designated as OC, OS1 and OS2 in

Strany 16 - [5] Pipe Processing

[ VII Control ] - 103 -HWE09120 GB-5- Bypass ControlBypass solenoid valves (SV1a), which bypass the high- and low- pressure sides, perform the follow

Strany 17 - [6] Brazing

[ VII Control ]- 104 -HWE09120 GB-6- Compressor Frequency Control Depending on the capacity required, the frequency of the compressor is controlled

Strany 18 - [7] Air Tightness Test

[ VII Control ] - 105 -HWE09120 GB-7- Defrost Operation Control(1) Starting the defrost operationThe defrost cycle will start when all of the three

Strany 19

[ VII Control ]- 106 -HWE09120 GB(3) Stopping the defrost operationThe defrost cycle ends when 12 minutes have passed since the beginning of the cyc

Strany 20 - [9] Refrigerant Charging

[ VII Control ] - 107 -HWE09120 GB-8- Refrigerant Recovery Control Recovery of refrigerant is performed during heating operation to prevent the refri

Strany 21

[ VII Control ]- 108 -HWE09120 GB-9- Capacity Control of Outdoor Fan(1) Control methodDepending on the capacity required, the rotation speed of the

Strany 22

[ VII Control ] - 109 -HWE09120 GB(2) P168, P192, P216, P240, P264, P288 models1 Qj:Total capacity (models) codeRefer to the VII [1] 2. (1) Dipswi

Strany 23 - [ I Read Before Servicing ]

[ VII Control ]- 110 -HWE09120 GB(3) P312, P336, P368 models1 Qj:Total capacity (models) codeRefer to the VII [1] 2. (1) Dipswitches for the capac

Strany 24 - Restrictions

[ I Read Before Servicing ] - 3 -HWE09120 GBI Read Before Servicing[1] Read Before Servicing1. Check the type of refrigerant used in the system to b

Strany 25

[ VII Control ] - 111 -HWE09120 GB-13- Emergency Operation Mode1. Problems with the outdoor unitEmergency operation mode is a temporary operation m

Strany 26 - [1] System configuration

[ VII Control ]- 112 -HWE09120 GB(2) Ending the emergency operation1) End conditionsWhen one of the following conditions is met, emergency operati

Strany 27

[ VII Control ] - 113 -HWE09120 GBEmergency operation pattern (2 outdoor units)Emergency operation pattern (3 outdoor units)(3) Ending the emergency

Strany 28

[ VII Control ]- 114 -HWE09120 GB-15- DEMAND ControlCooling/heating operation can be prohibited (Thermo-OFF) by an external input to the indoor units

Strany 29

[ VII Control ] - 115 -HWE09120 GB[3] Operation Flow Chart1. Mode determination flowchart (1) Indoor unit (cooling, heating, dry, fan mode)*Note 1. I

Strany 30

[ VII Control ]- 116 -HWE09120 GB(2) Outdoor unit (cooling and heating modes)*Note 1. For about 3 minutes after power on, search for the indoor unit

Strany 31 - Terminal

[ VII Control ] - 117 -HWE09120 GB2. Operations in each mode(1) Cooling operation*Note 1. The indoor fan operates at the set notch under cooling mod

Strany 32 - Example of wiring connection

[ VII Control ]- 118 -HWE09120 GB(2) Heating operation1) When outdoor unit starts defrosting, it transmits defrost operations command to indoor uni

Strany 33

[ VII Control ] - 119 -HWE09120 GB(3) Dry operationDry operation *Note 1 *Note 2 YES YES NO NO 4-way valve OFF 1. Outdoor unit (compressor) inte

Strany 34 - (*4, *5)

- 120 -[ VII Control ]GBHWE09120

Strany 35 - [4] Sample System Connection

[ I Read Before Servicing ]- 4 -HWE09120 GB[2] Necessary Tools and MaterialsPrepare the following tools and materials necessary for installing and se

Strany 36

- 121 -HWE09120 GBVIII Test Run Mode[1] Items to be checked before a Test Run...

Strany 38

[ VIII Test Run Mode ] - 123 -HWE09120 GBVIII Test Run Mode[1] Items to be checked before a Test Run(1) Check for refrigerant leak and loose cables a

Strany 39

[ VIII Test Run Mode ]- 124 -HWE09120 GB[2] Test Run MethodThe figure shows an MA remote controller (PAR-21MAA). PAR-21MAAON/OFF FILTERCHECKOPERATION

Strany 40

[ VIII Test Run Mode ] - 125 -HWE09120 GB[3] Operating Characteristic and Refrigerant AmountIt is important to have a clear understanding of the char

Strany 41 - M1 M2 M1 M2

[ VIII Test Run Mode ]- 126 -HWE09120 GB3. Amount of refrigerant to be addedThe amount of refrigerant that is shown in the table below is factory-ch

Strany 42

[ VIII Test Run Mode ] - 127 -HWE09120 GB(2) Example: PUHY-P168T(Y)SJMU-A(3) Sample calculationCAUTIONCharge liquid refrigerant (as opposed to gaseou

Strany 43 - M1 M2 M1 M2 M1 M2 M1 M2

[ VIII Test Run Mode ]- 128 -HWE09120 GB[5] Refrigerant Amount Adjust Mode1. Procedures Follow the procedures below to add or extract refrigerant as

Strany 44

[ VIII Test Run Mode ] - 129 -HWE09120 GBCAUTIONDo not release the extracted refrigerant into the air.CAUTIONCharge liquid refrigerant (as opposed to

Strany 45 - Group Group Group

[ VIII Test Run Mode ]- 130 -HWE09120 GB[6] The following symptoms are normal.SymptomsRemote controller displayCauseThe indoor unit does not start af

Strany 46

[ I Read Before Servicing ] - 5 -HWE09120 GB[3] Piping Materials1. Copper pipe materialsThe distinction between O-materials (Annealed) and 1/2H-mat

Strany 47

[ VIII Test Run Mode ] - 131 -HWE09120 GB[7] Standard Operation Data (Reference Data)1. Single unit(1) Cooling operationOperationOutdoor unit modelPU

Strany 48

[ VIII Test Run Mode ]- 132 -HWE09120 GBOperationOutdoor unit modelPUHY-P120TJMU-A PUHY-P144TJMU-AOperating conditionsAmbient tempera-tureIndoorDB/WB

Strany 49 - GBHWE09120

[ VIII Test Run Mode ] - 133 -HWE09120 GB(2) Heating operationOperationOutdoor unit modelPUHY-P72TJMU-A PUHY-P96TJMU-AOperating conditionsAmbient tem

Strany 50

[ VIII Test Run Mode ]- 134 -HWE09120 GBOperationOutdoor unit modelPUHY-P120TJMU-A PUHY-P144TJMU-AOperating conditionsAmbient tempera-tureIndoorDB/WB

Strany 51 - [623] or less)

[ VIII Test Run Mode ] - 135 -HWE09120 GB2. 2-unit combination(1) Cooling operationOperationOutdoor unit modelPUHY-P168TSJMU-APUHY-P72TJMU-A PUHY-P96

Strany 52

[ VIII Test Run Mode ]- 136 -HWE09120 GBOperationOutdoor unit modelPUHY-P192TSJMU-APUHY-P72TJMU-A PUHY-P120TJMU-AOperating conditionsAmbient tempera-

Strany 53

[ VIII Test Run Mode ] - 137 -HWE09120 GBOperationOutdoor unit modelPUHY-P216TSJMU-APUHY-P96TJMU-A PUHY-P120TJMU-AOperating conditionsAmbient tempera

Strany 54

[ VIII Test Run Mode ]- 138 -HWE09120 GBOperationOutdoor unit modelPUHY-P240TSJMU-APUHY-P120TJMU-A PUHY-P120TJMU-AOperating conditionsAmbient tempera

Strany 55

[ VIII Test Run Mode ] - 139 -HWE09120 GBOperationOutdoor unit modelPUHY-P264TSJMU-APUHY-P120TJMU-A PUHY-P144TJMU-AOperating conditionsAmbient temper

Strany 56 - Outdoor Unit Components

[ VIII Test Run Mode ]- 140 -HWE09120 GBOperationOutdoor unit modelPUHY-P288TSJMU-APUHY-P144TJMU-A PUHY-P144TJMU-AOperating conditionsAmbient tempera

Strany 57

[ I Read Before Servicing ]- 6 -HWE09120 GB4. Thickness and refrigerant type indicated on the piping materialsAsk the pipe manufacturer for the symb

Strany 58 - PUHY-P72, P96YJMU-A

[ VIII Test Run Mode ] - 141 -HWE09120 GB(2) Heating operationOperationOutdoor unit modelPUHY-P168TSJMU-APUHY-P72TJMU-A PUHY-P96TJMU-AOperating condi

Strany 59 - PUHY-P120, P144YJMU-A

[ VIII Test Run Mode ]- 142 -HWE09120 GBOperationOutdoor unit modelPUHY-P192TSJMU-APUHY-P72TJMU-A PUHY-P120TJMU-AOperating conditionsAmbient tempera-

Strany 60

[ VIII Test Run Mode ] - 143 -HWE09120 GBOperationOutdoor unit modelPUHY-P216TSJMU-APUHY-P96TJMU-A PUHY-P120TJMU-AOperating conditionsAmbient tempera

Strany 61 - (3) PUHY-P120, P144TJMU-A

[ VIII Test Run Mode ]- 144 -HWE09120 GBOperationOutdoor unit modelPUHY-P240TSJMU-APUHY-P120TJMU-A PUHY-P120TJMU-AOperating conditionsAmbient tempera

Strany 62 - <HIGH VOLTAGE WARNING>

[ VIII Test Run Mode ] - 145 -HWE09120 GBOperationOutdoor unit modelPUHY-P264TSJMU-APUHY-P120TJMU-A PUHY-P144TJMU-AOperating conditionsAmbient temper

Strany 63 - (R1,R5) Note.2

[ VIII Test Run Mode ]- 146 -HWE09120 GBOperationOutdoor unit modelPUHY-P288TSJMU-APUHY-P144TJMU-A PUHY-P144TJMU-AOperating conditionsAmbient tempera

Strany 64 - Transformer

[ VIII Test Run Mode ] - 147 -HWE09120 GB3. 3-unit combination(1) Cooling operationOperationOutdoor unit modelPUHY-P312TSJMU-APUHY-P72TJMU-APUHY-P120

Strany 65

[ VIII Test Run Mode ]- 148 -HWE09120 GBOperationOutdoor unit modelPUHY-P336TSJMU-APUHY-P96TJMU-APUHY-P120TJMU-APUHY-P120TJMU-AOperating conditionsAm

Strany 66 - 2. M-NET board

[ VIII Test Run Mode ] - 149 -HWE09120 GBOperationOutdoor unit modelPUHY-P360TSJMU-APUHY-P96TJMU-APUHY-P120TJMU-APUHY-P144TJMU-AOperating conditionsA

Strany 67

[ VIII Test Run Mode ]- 150 -HWE09120 GB(2) Heating operationOperationOutdoor unit modelPUHY-P312TSJMU-APUHY-P72TJMU-APUHY-P120TJMU-APUHY-P120TJMU-AO

Strany 68

[ I Read Before Servicing ] - 7 -HWE09120 GB[4] Storage of Piping1. Storage locationStore the pipes to be used indoors. (Warehouse at site or owner&a

Strany 69

[ VIII Test Run Mode ] - 151 -HWE09120 GBOperationOutdoor unit modelPUHY-P336TSJMU-APUHY-P96TJMU-APUHY-P120TJMU-APUHY-P120TJMU-AOperating conditionsA

Strany 70 - 4. Fan board

[ VIII Test Run Mode ]- 152 -HWE09120 GBOperationOutdoor unit modelPUHY-P360TSJMU-APUHY-P96TJMU-APUHY-P120TJMU-APUHY-P144TJMU-AOperating conditionsAm

Strany 71

- 153 -HWE09120 GBIX Troubleshooting[1] Error Code Lists...

Strany 73

[ IX Troubleshooting ] - 155 -HWE09120 GBIX Troubleshooting[1] Error Code ListsError CodePrelimi-nary error codeError (prelim-inary) detail codeError

Strany 74

[ IX Troubleshooting ]- 156 -HWE09120 GB5102 1217 -Temperature sensor faultIndoor unit pipe tempera-ture (TH22)OOA processing unit pipe temperature (

Strany 75

[ IX Troubleshooting ] - 157 -HWE09120 GBThe last digit in the check error codes in the 4000's and 5000's and two-digit detail codes indica

Strany 76 - Remote Controller

[ IX Troubleshooting ]- 158 -HWE09120 GB[2] Responding to Error Display on the Remote Controller1. Error CodeSerial communication error2. Error defi

Strany 77

[ IX Troubleshooting ] - 159 -HWE09120 GB1. Error CodeSerial communication error2. Error definition and error detection methodSerial communication e

Strany 78

[ IX Troubleshooting ]- 160 -HWE09120 GB1. Error CodeDischarge temperature fault 2. Error definition and error detection method1) If the discharge

Strany 79 - [ IV Remote Controller ]

[ I Read Before Servicing ]- 8 -HWE09120 GB[6] BrazingNo changes have been made in the brazing procedures. Perform brazing with special care to keep

Strany 80

[ IX Troubleshooting ] - 161 -HWE09120 GB1. Error CodeLow pressure fault 2. Error definition and error detection methodWhen starting the compressor

Strany 81

[ IX Troubleshooting ]- 162 -HWE09120 GB1. Error CodeHigh pressure fault 1 (Outdoor unit)2. Error definition and error detection method1) If the p

Strany 82

[ IX Troubleshooting ] - 163 -HWE09120 GB1. Error CodeHigh pressure fault 2 (Outdoor unit)2. Error definition and error detection methodIf the press

Strany 83

[ IX Troubleshooting ]- 164 -HWE09120 GB1. Error CodeDrain sensor submergence (Models with a drain sensor)2. Error definition and error detection me

Strany 84

[ IX Troubleshooting ] - 165 -HWE09120 GB1. Error CodeDrain sensor submergence (Models with a float switch)2. Error definition and error detection m

Strany 85

[ IX Troubleshooting ]- 166 -HWE09120 GB1. Error CodeDrain pump fault (Models with a drain sensor)2. Error definition and error detection method1)

Strany 86 - Electrical Wiring Diagram

[ IX Troubleshooting ] - 167 -HWE09120 GB1. Error CodeDrain pump fault (Models with a float switch)2. Error definition and error detection method1)

Strany 87

[ IX Troubleshooting ]- 168 -HWE09120 GB1. Error CodeDrain sensor (Thd) fault2. Error definition and error detection methodIf the open or short cir

Strany 88 - <Symbol explanation>

[ IX Troubleshooting ] - 169 -HWE09120 GB1. Error CodeWater leakage2. Cause, check method and remedyCheck that water does not leak from the pipes in

Strany 89

[ IX Troubleshooting ]- 170 -HWE09120 GB1. Error CodeOpen phase2. Error definition and error detection methodAn open phase of the power supply (L1

Strany 90

[ I Read Before Servicing ] - 9 -HWE09120 GB[7] Air Tightness TestNo changes have been made in the detection method. Note that a refrigerant leak det

Strany 91

[ IX Troubleshooting ] - 171 -HWE09120 GB1. Error CodeOpen phase2. Error definition and error detection methodAn open phase of the power supply (L1

Strany 92

[ IX Troubleshooting ]- 172 -HWE09120 GB1. Error Code<Transmission power supply fault Error detail code FF (Outdoor unit)>2. Error definition

Strany 93

[ IX Troubleshooting ] - 173 -HWE09120 GB1. Error CodeIndoor unit fan operation error2. Error definition and error detection method1) During opera

Strany 94 - Refrigerant Circuit

[ IX Troubleshooting ]- 174 -HWE09120 GB1. Error CodePower supply signal sync error2. Error definition and error detection methodThe frequency canno

Strany 95

[ IX Troubleshooting ] - 175 -HWE09120 GB1. Error CodeRPM error/Motor error 2. Error definition and error detection methodLOSSNAYThe motor keep ru

Strany 96 - (2) PUHY-P120, P144 models

[ IX Troubleshooting ]- 176 -HWE09120 GB1. Error CodeAbnormal bus voltage drop (Detail code 108)2. Error definition and error detection methodIf Vdc

Strany 97

[ IX Troubleshooting ] - 177 -HWE09120 GB1. Error CodeAbnormal bus voltage drop (Detail code 108)2. Error definition and error detection methodIf Vd

Strany 98 - 273 t

[ IX Troubleshooting ]- 178 -HWE09120 GB1. Error CodeAbnormal bus voltage rise (Detail code 109)2. Error definition and error detection methodIf Vdc

Strany 99

[ IX Troubleshooting ] - 179 -HWE09120 GB1. Error CodeLogic error (Detail code 111)2. Error definition and error detection methodH/W errorIf only th

Strany 100 - HWE09120 GB

[ IX Troubleshooting ]- 180 -HWE09120 GB1. Error CodeLogic error (Detail code 111)2. Error definition and error detection methodH/W errorIf only the

Strany 101 - [ VI Refrigerant Circuit ]

[ I Read Before Servicing ]- 10 -HWE09120 GB[8] Vacuum Drying (Evacuation)1. Vacuum pump with a reverse-flow check valve (Photo1)To prevent the vacu

Strany 102

[ IX Troubleshooting ] - 181 -HWE09120 GB1. Error CodeHeatsink overheat protection2. Error definition and error detection methodWhen the heat sink t

Strany 103

[ IX Troubleshooting ]- 182 -HWE09120 GB1. Error CodeHeatsink overheat protection2. Error definition and error detection methodWhen the heat sink te

Strany 104

[ IX Troubleshooting ] - 183 -HWE09120 GB1. Error CodeOverload protection2. Error definition and error detection methodIf the output current of &quo

Strany 105

[ IX Troubleshooting ]- 184 -HWE09120 GB1. Error CodeOverload protection2. Error definition and error detection methodIf the output current of &quo

Strany 106

[ IX Troubleshooting ] - 185 -HWE09120 GB1. Error CodeIPM error (Detail code 101)2. Error definition and error detection methodIn the case of 4250P7

Strany 107

[ IX Troubleshooting ]- 186 -HWE09120 GB1. Error CodeIPM error (Detail code 101)2. Error definition and error detection methodIn the case of 4250Ove

Strany 108 - Initial vane position

[ IX Troubleshooting ] - 187 -HWE09120 GB1. Error CodeDCCT overcurrent (H/W detection) (Detail code 103)Instantaneous overcurrent (Detail code 106)Ov

Strany 109 - Switch setting timing

[ IX Troubleshooting ]- 188 -HWE09120 GB1. Error CodeInstantaneous overcurrent (Detail code 106)Overcurrent (effective value) (Detail code 107)2. Er

Strany 110 - Rotary switch

[ IX Troubleshooting ] - 189 -HWE09120 GB1. Error CodeOvercurrent error due to short-circuited motor (Detail code 105)2. Error definition and error

Strany 111 - -4- Control at Start-up

[ IX Troubleshooting ]- 190 -HWE09120 GB1. Error CodeReturn air temperature sensor (TH21) fault (Indoor unit)Return air temperature sensor (TH4) faul

Strany 112 - -5- Bypass Control

ii HWE09120 GBSafety PrecautionsBefore installing the unit, thoroughly read the following safety precautions.Observe these safety precautions for yo

Strany 113

[ I Read Before Servicing ] - 11 -HWE09120 GB[9] Refrigerant Charging1. ReasonsR410A is a pseudo-azeotropic HFC blend (boiling point R32=-52°C[-62°F]

Strany 114 - -7- Defrost Operation Control

[ IX Troubleshooting ] - 191 -HWE09120 GB1. Error CodeHIC bypass circuit outlet temperature sensor (TH2) fault (Outdoor unit)Heat exchanger outlet te

Strany 115

[ IX Troubleshooting ]- 192 -HWE09120 GB1. Error CodeHeatsink temperature sensor (THHS) fault (Detail code 01)2. Error definition and error detectio

Strany 116 - 30 seconds

[ IX Troubleshooting ] - 193 -HWE09120 GB1. Error CodeHeatsink temperature sensor (THHS) fault (Detail code 01)2. Error definition and error detecti

Strany 117

[ IX Troubleshooting ]- 194 -HWE09120 GB1. Error CodeACCT sensor fault (Detail code 115)2. Error definition and error detection methodWhen the formu

Strany 118 - [ VII Control ]

[ IX Troubleshooting ] - 195 -HWE09120 GB1. Error CodeACCT sensor fault (Detail code 115)2. Error definition and error detection methodWhen the form

Strany 119 - (3) P312, P336, P368 models

[ IX Troubleshooting ]- 196 -HWE09120 GB1. Error CodeDCCT sensor circuit fault (Detail code118)2. Error definition and error detection methodWhen an

Strany 120 - -13- Emergency Operation Mode

[ IX Troubleshooting ] - 197 -HWE09120 GB1. Error CodeOpen-circuited IPM/Loose ACCT connector (Detail code 119)2. Error definition and error detecti

Strany 121

[ IX Troubleshooting ]- 198 -HWE09120 GB1. Error CodeFaulty ACCT wiring (Detail code 120)2. Error definition and error detection methodPresence of t

Strany 122 - -14- Operation Mode

[ IX Troubleshooting ] - 199 -HWE09120 GB1. Error CodeLoose float switch connector2. Error definition and error detection methodDetection of the dis

Strany 123 - -15- DEMAND Control

[ IX Troubleshooting ]- 200 -HWE09120 GB1. Error CodeAddress overlap2. Error definition and error detection methodAn error in which signals from mor

Strany 124 - [3] Operation Flow Chart

[ I Read Before Servicing ]- 12 -HWE09120 GB[11] Characteristics of the Conventional and the New Refrigerants1. Chemical propertyAs with R22, the new

Strany 125

[ IX Troubleshooting ] - 201 -HWE09120 GB1. Error CodeTransmission processor hardware error2. Error definition and error detection methodAlthough &q

Strany 126 - (1) Cooling operation

[ IX Troubleshooting ]- 202 -HWE09120 GB1. Error CodeTransmission line bus busy error 2. Error definition and error detection methodGenerated error

Strany 127 - Thermostat ON

[ IX Troubleshooting ] - 203 -HWE09120 GB1. Error CodeNo ACK error 2. Error definition and error detection methodThe error is detected when no ackno

Strany 128 - 18°C[64°F]

[ IX Troubleshooting ]- 204 -HWE09120 GB1. Error CodeNo ACK error 2. Error definition and error detection methodThe error is detected when no acknow

Strany 129

[ IX Troubleshooting ] - 205 -HWE09120 GB1. Error CodeNo ACK error 2. Error definition and error detection methodThe error is detected when no ackno

Strany 130 - Test Run Mode

[ IX Troubleshooting ]- 206 -HWE09120 GB1. Error CodeNo ACK error 2. Error definition and error detection methodThe error is detected when no acknow

Strany 131

[ IX Troubleshooting ] - 207 -HWE09120 GB1. Error CodeNo ACK error 2. Error definition and error detection methodThe error is detected when no ackno

Strany 132

[ IX Troubleshooting ]- 208 -HWE09120 GB1. Error CodeNo ACK error 2. Error definition and error detection methodThe error is detected when no acknow

Strany 133 - [2] Test Run Method

[ IX Troubleshooting ] - 209 -HWE09120 GB1. Error CodeNo ACK error 2. Error definition and error detection methodThe error is detected when no ackno

Strany 134

[ IX Troubleshooting ]- 210 -HWE09120 GB1. Error CodeNo ACK error 2. Error definition and error detection methodThe error is detected when no acknow

Strany 135

[ I Read Before Servicing ] - 13 -HWE09120 GB[12] Notes on Refrigerating Machine Oil1. Refrigerating machine oil in the HFC refrigerant systemHFC ty

Strany 136 - Liquid

[ IX Troubleshooting ] - 211 -HWE09120 GB1. Error CodeNo response error 2. Error definition and error detection methodWhen no response command is r

Strany 137 - Self-diagnosis swithes on Tc

[ IX Troubleshooting ]- 212 -HWE09120 GB1. Error CodeMA controller signal reception error (No signal reception)2. Error definition and error detecti

Strany 138 - OC, OS1, and OS2.)

[ IX Troubleshooting ] - 213 -HWE09120 GB1. Error CodeMA remote controller signal transmission error (Synchronization error)2. Error definition and

Strany 139

[ IX Troubleshooting ]- 214 -HWE09120 GB1. Error CodeMA remote controller signal transmission error (Hardware error)2. Error definition and error de

Strany 140

[ IX Troubleshooting ] - 215 -HWE09120 GB1. Error CodeMA controller signal reception error (Start bit detection error)2. Error definition and error

Strany 141

[ IX Troubleshooting ]- 216 -HWE09120 GB1. Error CodeTotal capacity error2. Error definition and error detection methodThe model total of indoor uni

Strany 142

[ IX Troubleshooting ] - 217 -HWE09120 GB1. Error CodeCapacity code setting error2. Error definition and error detection method Connection of incomp

Strany 143

[ IX Troubleshooting ]- 218 -HWE09120 GB1. Error CodeWrong number of connected units2. Error definition and error detection method The number of con

Strany 144

[ IX Troubleshooting ] - 219 -HWE09120 GB1. Error CodeAddress setting error2. Error definition and error detection methodErroneous setting of OC uni

Strany 145

[ IX Troubleshooting ]- 220 -HWE09120 GB1. Error CodeConnection information signal transmission/reception error2. Error definition and error detecti

Strany 146

- 14 -[ I Read Before Servicing ]GBHWE09120

Strany 147

[ IX Troubleshooting ] - 221 -HWE09120 GB1. Error CodeFunction setting error (incorrect resistor connection)2. Error source, cause, check method and

Strany 148

[ IX Troubleshooting ]- 222 -HWE09120 GB1. Error CodeModel setting error2. Error source, cause, check method and remedy7117Error source Cause Check

Strany 149

[ IX Troubleshooting ] - 223 -HWE09120 GB1. Error CodeIncompatible unit combination 2. Error definition and error detection methodThe check code wil

Strany 150

[ IX Troubleshooting ]- 224 -HWE09120 GB-1- Troubleshooting according to the remote controller malfunction or the external input errorIn the case of

Strany 151

[ IX Troubleshooting ] - 225 -HWE09120 GBIn the case of MA remote controller2. PhenomenaWhen the remote controller operation SW is turned on, the ope

Strany 152

[ IX Troubleshooting ]- 226 -HWE09120 GBIn the case of MA remote controller3. Phenomena"HO" or "PLEASE WAIT" display on the remot

Strany 153

[ IX Troubleshooting ] - 227 -HWE09120 GBFlow chartEven if the operation button on the remote controller is pressed, the indoor and the outdoor units

Strany 154

[ IX Troubleshooting ]- 228 -HWE09120 GBIn case of ME remote controller1. PhenomenaEven if the operation button on the remote controller is pressed,

Strany 155

[ IX Troubleshooting ] - 229 -HWE09120 GBIn case of ME remote controller2. PhenomenaWhen the remote controller operation SW is turned on, a temporary

Strany 156

[ IX Troubleshooting ]- 230 -HWE09120 GBIn case of ME remote controller3. Phenomena"HO" display on the remote controller does not disappear

Strany 157

- 15 -HWE09120 GBII Restrictions[1] System configuration ...

Strany 158

[ IX Troubleshooting ] - 231 -HWE09120 GBIn case of ME remote controller4. Phenomena"88" appears on the remote controller when the address

Strany 159

[ IX Troubleshooting ]- 232 -HWE09120 GBBoth for MA remote controller and ME remote controller1. PhenomenaAlthough cooling operation starts with the

Strany 160

[ IX Troubleshooting ] - 233 -HWE09120 GBCause Check method and remedy4. Long piping lengthThe cooling capacity varies greatly depending on the press

Strany 161

[ IX Troubleshooting ]- 234 -HWE09120 GB2. PhenomenaAlthough heating operation starts with the normal remote controller display, the capacity is not

Strany 162 - Troubleshooting

[ IX Troubleshooting ] - 235 -HWE09120 GBCause Check method and remedy2. Indoor unit LEV malfunctionInsufficient refrigerant flows due to LEV malfunc

Strany 163

[ IX Troubleshooting ]- 236 -HWE09120 GB3. PhenomenaOutdoor unit stops at times during operation.(1) Cause, check method and remedyCause Check metho

Strany 164 - Remote controller

[ IX Troubleshooting ] - 237 -HWE09120 GB[3] Investigation of Transmission Wave Shape/Noise1. M-NET transmissionControl is performed by exchanging si

Strany 165

[ IX Troubleshooting ]- 238 -HWE09120 GB(3) Check method and remedy1) Measures against noiseCheck the followings when noise exists on the wave or

Strany 166

[ IX Troubleshooting ] - 239 -HWE09120 GB2. MA remote controller transmissionThe communication between the MA remote controller and the indoor unit

Strany 167 - 0403 (TJMU-A) (Indoor unit)

[ IX Troubleshooting ]- 240 -HWE09120 GB[4] Troubleshooting Principal Parts-1- High-Pressure Sensor (63HS1)1. Compare the pressure that is detected

Strany 169

[ IX Troubleshooting ] - 241 -HWE09120 GB-2- Low-Pressure Sensor (63LS)1. Compare the pressure that is detected by the low pressure sensor, and the

Strany 170

[ IX Troubleshooting ]- 242 -HWE09120 GB-3- Solenoid ValveCheck whether the output signal from the control board and the operation of the solenoid va

Strany 171 - +0,-0.15

[ IX Troubleshooting ] - 243 -HWE09120 GB(3) In case of SV1a (Bypass valve)This solenoid valve opens when powered (Relay ON).1) At compressor star

Strany 172

[ IX Troubleshooting ]- 244 -HWE09120 GBYESYESYESYESYESNONONONOReplace the control board.Replace 52F.Is the wiring between the FAN board, 52F, and fa

Strany 173

[ IX Troubleshooting ] - 245 -HWE09120 GB-5- LEVLEV operationLEV (Indoor unit: Linear expansion valve), LEV2 (Outdoor unit: Linear expansion valve) a

Strany 174

[ IX Troubleshooting ]- 246 -HWE09120 GB4) LEV closing and opening operation*Upon power on, the indoor unit circuit board sends a 2200 pulse signa

Strany 175

[ IX Troubleshooting ] - 247 -HWE09120 GB(2) Outdoor LEV (LEV1)The valve opening changes according to the number of pulses.1) Connections between

Strany 176

[ IX Troubleshooting ]- 248 -HWE09120 GB(3) Judgment methods and possible failure modeThe specifications of the outdoor unit (outdoor LEV) and the i

Strany 177

[ IX Troubleshooting ] - 249 -HWE09120 GB(4) Outdoor unit LEV (LEV1) coil removal procedure1) LEV componentAs shown in the figure, the outdoor LEV

Strany 178

[ IX Troubleshooting ]- 250 -HWE09120 GB(5) Removal procedure of outdoor unit LEV2 coil1) ComponentsThe outdoor unit LEV consists of a coil and a

Strany 179 - 4102 (TJMU-A)

[ II Restrictions ] - 17 -HWE09120 GBII Restrictions[1] System configuration1. Table of compatible indoor unitsThe table below summarizes the types o

Strany 180 - 4102 (YJMU-A)

[ IX Troubleshooting ] - 251 -HWE09120 GB-6- Inverter (TJMU-A)Replace only the compressor if only the compressor is found to be defective. (Overcurr

Strany 181

[ IX Troubleshooting ]- 252 -HWE09120 GBError display/failure condition Measure/inspection item[1] Inverter related errors4250, 4255, 4220, 4225, 423

Strany 182

[ IX Troubleshooting ] - 253 -HWE09120 GB(2) Inverter output related troublesItems to be checked Phenomena Remedy[1]Check the INV board error detect

Strany 183 - (TJMU-A)

[ IX Troubleshooting ]- 254 -HWE09120 GBItems to be checked Phenomena Remedy[3]Check whether the inverter is damaged.(No load)<P72 model> 1) In

Strany 184

[ IX Troubleshooting ] - 255 -HWE09120 GB[4]Check whether the inverter is damaged.(During com-pressor opera-tion)Put the outdoor unit into oper-ation

Strany 185

[ IX Troubleshooting ]- 256 -HWE09120 GB(3) Trouble treatment when the main power breaker is tripped.Items to be checked Phenomena Remedy[1] Perform

Strany 186 - (YJMU-A)

[ IX Troubleshooting ] - 257 -HWE09120 GB(4) Simple checking procedure for individual components of main inverter circuitBefore checking, turn the po

Strany 187

[ IX Troubleshooting ]- 258 -HWE09120 GB(5) Intelligent power module (P96, P120, P144 models)Measure resistances between each pair of terminals on t

Strany 188

[ IX Troubleshooting ] - 259 -HWE09120 GB(6) Diode stack (P96, P120, P144 models)Measure resistances between each pair of terminals on the diode sta

Strany 189

[ IX Troubleshooting ]- 260 -HWE09120 GBINV board external diagramFaston terminals have a locking function. Make sure the cable heads are securely lo

Strany 190 - 4230 (TJMU-A)

[ II Restrictions ]- 18 -HWE09120 GB[2] Types and Maximum allowable Length of Cables1. Wiring work (1) Notes1) Have all electrical work performed b

Strany 191 - 4230 (YJMU-A)

[ IX Troubleshooting ] - 261 -HWE09120 GB-6- Inverter (YJMU-A)Replace only the compressor if only the compressor is found to be defective. Replace

Strany 192 - 4240 (TJMU-A)

[ IX Troubleshooting ]- 262 -HWE09120 GBError display/failure condition Measure/inspection item[1] Inverter related errors4250, 4255, 4220, 4225, 423

Strany 193 - 4240 (YJMU-A)

[ IX Troubleshooting ] - 263 -HWE09120 GB(2) Inverter output related troublesItems to be checked Phenomena Remedy[1]Check the INV board er-ror detec

Strany 194

[ IX Troubleshooting ]- 264 -HWE09120 GBItems to be checked Phenomena Remedy[4]Check whether the inverter is damaged.(During com-pressor opera-tion)P

Strany 195

[ IX Troubleshooting ] - 265 -HWE09120 GB(3) Trouble treatment when the main power breaker is tripped(4) Trouble treatment when the main power eart

Strany 196 - 4250 (TJMU-A)

[ IX Troubleshooting ]- 266 -HWE09120 GB(5) Simple checking procedure for individual components of main inverter circuitBefore inspecting the inside

Strany 197 - 4250 (YJMU-A)

[ IX Troubleshooting ] - 267 -HWE09120 GBINV board external diagramJudgment value (reference)Black ( + )SC-P1 FT-N SC-L1 SC-L2 SC-L3Red (-)SC-P1 - -

Strany 198 - 4260 (YJMU-A)

[ IX Troubleshooting ]- 268 -HWE09120 GB-7- Control Circuit (TJMU-A)(1) Control power source function block1) PUHY-P72TJMU-AOutdoor unit Power sou

Strany 199

[ IX Troubleshooting ] - 269 -HWE09120 GB2) PUHY-P96, P120, P144TJMU-A * MA remote controllers and ME remote controllers cannot be used together.(B

Strany 200

[ IX Troubleshooting ]- 270 -HWE09120 GB(2) Troubleshooting transmission power circuit of outdoor unit1) PUHY-P72TJMU-ACheck the voltage between N

Strany 201

[ II Restrictions ] - 19 -HWE09120 GB2) Remote controller wiring*1 MA remote controller refers to MA remote controller (PAR-20MAU, PAR-21MAA), MA

Strany 202 - 5110 (YJMU-A)

[ IX Troubleshooting ] - 271 -HWE09120 GB2) PUHY-P96, P120, P144TJMU-ADC24 ~ 30V YES NO NO NO NO Check the voltage at the indoor/outdoor transmiss

Strany 203 - 5301 (TJMU-A)

[ IX Troubleshooting ]- 272 -HWE09120 GB-7- Control Circuit (YJMU-A)(1) Control power source function block1) PUHY-P72, P96, P120, P144YJMU-AOutdoo

Strany 204 - 5301 (YJMU-A)

[ IX Troubleshooting ] - 273 -HWE09120 GB(2) Troubleshooting transmission power circuit of outdoor unit1) PUHY-P72, P96, P120, P144YJMU-AYESYESYES

Strany 205

[ IX Troubleshooting ]- 274 -HWE09120 GB[5] Refrigerant Leak1. Leak spot: In the case of extension pipe for indoor unit (Cooling season)1) Mount a

Strany 206

[ IX Troubleshooting ] - 275 -HWE09120 GBWhen the power to the outdoor/indoor unit must be turned off to repair the leak after closing the service va

Strany 207

[ IX Troubleshooting ]- 276 -HWE09120 GB[6] Compressor Replacement Instructions Transformerbox*1Follow the procedures below (Steps 1 through 6) to

Strany 208

[ IX Troubleshooting ] - 277 -HWE09120 GB Compressor cover (top) 4. Remove the compressor cover (top). 5. Remove the compressor wires, compressor

Strany 209

[ IX Troubleshooting ]- 278 -HWE09120 GB[7] Troubleshooting Using the Outdoor Unit LED Error DisplayIf the LED error display appear as follows while

Strany 210

- 279 -HWE09120 GBX LED Monitor Display on the Outdoor Unit Board[1] How to Read the LED on the Service Monitor ...

Strany 211

- 280 -

Strany 212

[ II Restrictions ]- 20 -HWE09120 GB2. M-NET Address settings(1) Address settings tableThe need for address settings and the range of address settin

Strany 213

[ X LED Monitor Display on the Outdoor Unit Board ] - 281 -HWE09120 GBX LED Monitor Display on the Outdoor Unit Board[1] How to Read the LED on the S

Strany 214

[ X LED Monitor Display on the Outdoor Unit Board ]- 282 -HWE09120 GB3. Time data storage functionThe outdoor unit has a simple clock function that

Strany 215

[ X LED Monitor Display on the Outdoor Unit Board ]- 283 -HWE09120ILED Monitor Di splay on the Outdoor Unit Bo ardLED monitor displayCurrent dataNo.

Strany 216

[ X LED Monitor Display on the Outdoor Unit Board ]- 284 -HWE0912011 1101000000External signal(Open input contact point)Contact point de-mandLow-nois

Strany 217

[ X LED Monitor Display on the Outdoor Unit Board ]- 285 -HWE0912024 0001100000Indoor unit thermo-statTop Unit No. 1 Unit No. 2 Unit No. 3 Unit No. 4

Strany 218

[ X LED Monitor Display on the Outdoor Unit Board ]- 286 -HWE0912045 1011010000 TH4 -99.9 to 999.9 A A The unit is [°C]46 0111010000 TH3 -99.9 to 999

Strany 219

[ X LED Monitor Display on the Outdoor Unit Board ]- 287 -HWE0912072 000100100073 100100100074 010100100075 110100100076 001100100077 101100100078 01

Strany 220

[ X LED Monitor Display on the Outdoor Unit Board ]- 288 -HWE0912094 0111101000 AK 0000 to 9999 A A95 1111101000 FAN 0000 to 9999 A A Fan output [ %

Strany 221

[ X LED Monitor Display on the Outdoor Unit Board ]- 289 -HWE09120117 1010111000COMP Operation timeUpper 4 digits0000 to 9999 A AThe unit is [ h ]118

Strany 222

[ X LED Monitor Display on the Outdoor Unit Board ]- 290 -HWE09120139 1101000100140 0011000100141 1011000100142 0111000100143 1111000100144 000010010

Strany 223

iiHWE09120 GBWARNINGSecurely attach the terminal block cover (panel) to the unit.If the terminal block cover (panel) is not installed properly, dust a

Strany 224

[ II Restrictions ] - 21 -HWE09120 GB(2) Power supply switch connector connection on the outdoor unit(Factory setting: The male power supply switch c

Strany 225

[ X LED Monitor Display on the Outdoor Unit Board ]- 291 -HWE09120167 1110010100 168 0001010100 169 1001010100 170 0101010100 171 1101010100 172 0011

Strany 226

[ X LED Monitor Display on the Outdoor Unit Board ]- 292 -HWE09120178 0100110100 Error history 1 0000 to 9999 B B Address and error codes highlighted

Strany 227

[ X LED Monitor Display on the Outdoor Unit Board ]- 293 -HWE09120Error historyNo.SW1ItemDisplayUnit(A, B) *1Remarks1234567890 LD1 LD2 LD3 LD4 LD5 LD

Strany 228

[ X LED Monitor Display on the Outdoor Unit Board ]- 294 -HWE09120216 0001101100 TH4 -99.9 to 999.9 A A The unit is [°C]217 1001101100 TH3 -99.9 to 9

Strany 229

[ X LED Monitor Display on the Outdoor Unit Board ]- 295 -HWE09120243 1100111100244 0010111100245 1010111100246 0110111100247 1110111100248 000111110

Strany 230

[ X LED Monitor Display on the Outdoor Unit Board ]- 296 -HWE09120268 0011000010269 1011000010270 0111000010271 1111000010272 0000100010273 100010001

Strany 231

[ X LED Monitor Display on the Outdoor Unit Board ]- 297 -HWE09120293 1010010010294 0110010010COMP number of start-stop eventsUpper 4 digits0000 to 9

Strany 232

[ X LED Monitor Display on the Outdoor Unit Board ]- 298 -HWE09120Current dataNo.SW1ItemDisplayUnit(A, B)*1Remarks1234567890 LD1 LD2 LD3 LD4 LD5 LD6

Strany 233

[ X LED Monitor Display on the Outdoor Unit Board ]- 299 -HWE09120328 0001001010 329 1001001010 330 0101001010 331 1101001010 332 0011001010 333 1011

Strany 234 - Is the error code 7102

[ X LED Monitor Display on the Outdoor Unit Board ]- 300 -HWE09120Data on indoor unit systemNo.SW1ItemDisplayUnit(A, B) *1Remarks1234567890 LD1 LD2 L

Strany 235

[ II Restrictions ]- 22 -HWE09120 GB(6) Miscellaneous settingsCooling-only setting for the indoor unit: Cooling only model (Factory setting: SW3-1 &q

Strany 236 - Flow chart

[ X LED Monitor Display on the Outdoor Unit Board ]- 301 -HWE09120368 0000111010 IC18 Address/capacity code 0000 to 9999 0000 to 9999 B Displayed alt

Strany 237

[ X LED Monitor Display on the Outdoor Unit Board ]- 302 -HWE09120396 0011000110 IC46 Address/capacity code 0000 to 9999 0000 to 9999 B Displayed alt

Strany 238 - Connector contact failure

[ X LED Monitor Display on the Outdoor Unit Board ]- 303 -HWE09120412 0011100110 IC5 Suction temperature -99.9 to 999.9 B The unit is [°C]413 1011100

Strany 239

[ X LED Monitor Display on the Outdoor Unit Board ]- 304 -HWE09120436 0010110110 IC29 Suction temperature -99.9 to 999.9 B The unit is [°C]437 101011

Strany 240

[ X LED Monitor Display on the Outdoor Unit Board ]- 305 -HWE09120464 0000101110 IC7 Liquid pipe temperature -99.9 to 999.9 B The unit is [°C]465 100

Strany 241 - Evaporating temperature Te

[ X LED Monitor Display on the Outdoor Unit Board ]- 306 -HWE09120492 0011011110 IC35 Liquid pipe temperature -99.9 to 999.9 B The unit is [°C]493 10

Strany 242

[ X LED Monitor Display on the Outdoor Unit Board ]- 307 -HWE09120Setting dataNo.SW1ItemDisplayUnit(A, B)*1Remarks1234567890 LD1 LD2 LD3 LD4 LD5 LD6

Strany 243 - Condensing temperature Tc

[ X LED Monitor Display on the Outdoor Unit Board ]- 308 -HWE09120Data on indoor unit systemNo.SW1ItemDisplayUnit(A, B) *1Remarks1234567890 LD1 LD2 L

Strany 244

[ X LED Monitor Display on the Outdoor Unit Board ]- 309 -HWE09120Data on indoor unit systemNo.SW1ItemDisplayUnit(A, B) *1Remarks1234567890 LD1 LD2 L

Strany 245

[ X LED Monitor Display on the Outdoor Unit Board ]- 310 -HWE09120Data on indoor unit systemNo.SW1ItemDisplayUnit(A, B)*1Remarks1234567890 LD1 LD2 LD

Strany 246 - [Without transmission]

[ II Restrictions ] - 23 -HWE09120 GBExample of wiring connection(1) CN51(2) CN3SCN51XYL1L2ecruos rewop pmaLDistant control boardRelay circuit Adapte

Strany 247

[ X LED Monitor Display on the Outdoor Unit Board ]- 311 -HWE09120600 0001101001 IC28SH -99.9 to 999.9 B The unit is [ °C ] 601 1001101001 IC29SH -99

Strany 248

[ X LED Monitor Display on the Outdoor Unit Board ]- 312 -HWE09120Data on indoor unit systemNo.SW1ItemDisplayUnit(A, B)*1Remarks1234567890 LD1 LD2 LD

Strany 249 - Vout 0.5 ~ 3.5 V

[ X LED Monitor Display on the Outdoor Unit Board ]- 313 -HWE09120650 0101000101 IC28SC -99.9 to 999.9 B The unit is [ °C ] 651 1101000101 IC29SC -9

Strany 250 - Vout 0.5 ~ 3.5 V

[ X LED Monitor Display on the Outdoor Unit Board ]- 314 -HWE09120Setting dataNo.SW1ItemDisplayUnit(A, B)* 1Remarks1234567890 LD1 LD2 LD3 LD4 LD5 LD6

Strany 251 - -3- Solenoid Valve

[ X LED Monitor Display on the Outdoor Unit Board ]- 315 -HWE09120688 0000110101 Current time 00:00 to 23:59 A A Hour: minute689 1000110101 Current

Strany 252 - 12345678 9 10

[ X LED Monitor Display on the Outdoor Unit Board ]- 316 -HWE09120702 0111110101 Time of error detection 7 00:00 to 23:59 A A Hour: minute703 111111

Strany 253

[ X LED Monitor Display on the Outdoor Unit Board ]- 317 -HWE09120Data on indoor unit systemNo.SW1ItemDisplayUnit(A, B)* 1Remarks1234567890 LD1 LD2 L

Strany 254

[ X LED Monitor Display on the Outdoor Unit Board ]- 318 -HWE09120741 1010011101 IC28 LEV opening 0000 to 9999 B Fully open: 2000742 0110011101 IC2

Strany 255

[ X LED Monitor Display on the Outdoor Unit Board ]- 319 -HWE09120769 1000000011 IC6 Operation mode0000 : Stop 0001 : Ventilation 0002 : Cooling

Strany 256 - 12345678

[ X LED Monitor Display on the Outdoor Unit Board ]- 320 -HWE09120797 1011100011 IC34 Operation mode0000 : Stop 0001 : Ventilation 0002 : Cooling

Strany 257 - Linear Expansion Valve

[ II Restrictions ]- 24 -HWE09120 GB3. Demand control(1) General outline of controlDemand control is performed by using the external signal input to

Strany 258 - Lead wire

[ X LED Monitor Display on the Outdoor Unit Board ]- 321 -HWE09120825 1001110011 IC12 filter 0000 to 9999 B Hours since last mainte-nance [ h ]826 0

Strany 259

[ X LED Monitor Display on the Outdoor Unit Board ]- 322 -HWE09120853 1010101011 IC40 filter 0000 to 9999 B Hours since last mainte-nance [ h ]854

Strany 260 - -6- Inverter (TJMU-A)

[ X LED Monitor Display on the Outdoor Unit Board ]- 323 -HWE09120Other types of dataNo.SW1ItemDisplayUnit(A, B) *1Remarks1234567890 LD1 LD2 LD3 LD4

Strany 261

[ X LED Monitor Display on the Outdoor Unit Board ]- 324 -HWE09120887 1110111011 888 0001111011 889 1001111011 890 0101111011 891 1101111011 892 0011

Strany 262

PUHY-P72, P96, P120, P144T(Y)JMU-APUHY-P168, P192, P216, P240, P264, P288T(Y)SJMU-APUHY-P312, P336, P360T(Y)SJMU-AIssued in Feb. 2010 HWE09120Printed

Strany 263

[ II Restrictions ] - 25 -HWE09120 GB2) When SW4-4 on one outdoor unit in one refrigerant circuit system is set to ON (4 levels of on-DEMAND) (*3)*

Strany 264

[ II Restrictions ]- 26 -HWE09120 GB[4] Sample System ConnectionExamples of typical system connection are shown on pages [5] to [7]. Refer to the Ins

Strany 265

[ II Restrictions ] - 27 -HWE09120 GB

Strany 266 - Installation direction

- 28 -[ II Restrictions ]GBHWE09120[5] An Example of a System to which an MA Remote Controller is connected1. System with one outdoor unit (automati

Strany 267

[ II Restrictions ] 29- 29 -HWE09120 GB(4) Wiring method1) Indoor/outdoor transmission lineDaisy-chain terminals M1 and M2 on the terminal block fo

Strany 268 - L1 L2 L3

- 30 -[ II Restrictions ]GBHWE091202. An example of a system with one outdoor unit to which 2 or more LOSSNAY units are connected (manual address se

Strany 269 - SC-USC-RSC-SSC-TTB-N(Note)

iiiiii HWE09120 GBPrecautions for handling units for use with R410ACAUTIONDo not use the existing refrigerant piping.A large amount of chlorine that

Strany 270 - -6- Inverter (YJMU-A)

[ II Restrictions ] 31- 31 -HWE09120 GB(4) Wiring method1) Indoor/outdoor transmission lineSame as [5] 1.Shielded cable connectionSame as [5] 1.2)

Strany 271

- 32 -[ II Restrictions ]GBHWE091203. Group operation of units in a system with multiple outdoor units(1) Sample control wiring(2) Cautions1) ME r

Strany 272

[ II Restrictions ] 33- 33 -HWE09120 GB(4) Wiring method1) Indoor/outdoor transmission lineSame as [5] 1.Only use shielded cables.Shielded cable c

Strany 273

- 34 -[ II Restrictions ]GBHWE091204. A system in which a system controller is connected to the transmission line for centralized control and which

Strany 274

[ II Restrictions ] 35- 35 -HWE09120 GB(4) Wiring method1) Indoor/outdoor transmission lineSame as [5] 1.Only use shielded cables.Shielded cable co

Strany 275 - (Center value 75 ohm)

- 36 -[ II Restrictions ]GBHWE091205. An example of a system in which a system controller is connected to the indoor-outdoor transmission line (exce

Strany 276

[ II Restrictions ] 37- 37 -HWE09120 GB(4) Wiring method1) Indoor/outdoor transmission lineDaisy-chain terminals M1 and M2 on the terminal block fo

Strany 277 - -7- Control Circuit (TJMU-A)

- 38 -[ II Restrictions ]GBHWE09120[6] An Example of a System to which an ME Remote Controller is connected(1) Sample control wiring(2) Cautions1)

Strany 278

[ II Restrictions ] 39- 39 -HWE09120 GB(4) Wiring method1) Indoor/outdoor transmission lineSame as [5] 1.Shielded cable connectionSame as [5] 1.2)

Strany 279 - 1) PUHY-P72TJMU-A

- 40 -[ II Restrictions ]GBHWE09120[7] An Example of a System to which both MA Remote Controller and ME Remote Controller are connected(1) Sample con

Strany 280

ivHWE09120 GBBefore installing the unitWARNINGDo not install the unit where a gas leak may occur.If gaseous refrigerant leaks and piles up around the

Strany 281 - Oudoor unit

[ II Restrictions ] 41- 41 -HWE09120 GB(4) Wiring method1) Indoor/outdoor transmission lineSame as [5] 3.Shielded cable connectionSame as [5] 1.2)

Strany 282

[ II Restrictions ]- 42 -HWE09120 GB[8] Restrictions on Pipe Length(1) End branchingP72 - P144 modelsUnit: m [ft]Operation Pipe sectionsAllowable len

Strany 283 - [5] Refrigerant Leak

[ II Restrictions ] - 43 -HWE09120 GBP168 - P360 modelsThe figure shows a system with three outdoor units. (P312-P360 models)Unit: m [ft]Operation Pi

Strany 284

[ II Restrictions ]- 44 -HWE09120 GB1. Refrigerant pipe size(1) Diameter of the refrigerant pipe between the outdoor unit and the first branch (outdo

Strany 285

[ II Restrictions ] - 45 -HWE09120 GB(4) Size of the refrigerant pipe between the first distributor and the second distributor(5) Size of the refri

Strany 286 - (right and left)

- 46 -[ II Restrictions ]GBHWE09120

Strany 287

- 47 -HWE09120 GBIII Outdoor Unit Components[1] Outdoor Unit Components and Refrigerant Circuit ...

Strany 289

[ III Outdoor Unit Components ] - 49 -HWE09120 GBIII Outdoor Unit Components[1] Outdoor Unit Components and Refrigerant Circuit1. Front view of a ou

Strany 290 - 7SEG LED

[ III Outdoor Unit Components ]- 50 -HWE09120 GB(2) PUHY-P120, P144TJMU-APUHY-P120, P144YJMU-AFanControl Control BoxBoxControl boxFan guardFin guardF

Strany 291 - Day count

vv HWE09120 GBBefore installing the unit (moving and reinstalling the unit) and performing electrical workCAUTIONProperly ground the unit.Do not conne

Strany 292 - Current data

[ III Outdoor Unit Components ] - 51 -HWE09120 GB2. Refrigerant circuit(1) PUHY-P72TJMU-APUHY-P72YJMU-A(2) PUHY-P96TJMU-APUHY-P96YJMU-AHigh-pressure

Strany 293

[ III Outdoor Unit Components ]- 52 -HWE09120 GB(3) PUHY-P120, P144TJMU-APUHY-P120, P144YJMU-AThe YJMU model has a transformer box.High-pressure sens

Strany 294

[ III Outdoor Unit Components ] - 53 -HWE09120 GB[2] Control Box of the Outdoor Unit1. PUHY-P72, P96TJMU-A1) Exercise caution not to damage the bot

Strany 295

[ III Outdoor Unit Components ]- 54 -HWE09120 GB2. PUHY-P96, P120, P144TJMU-A3. PUHY-P72, P96, P120, P144YJMU-A1) Exercise caution not to damage

Strany 296

[ III Outdoor Unit Components ] - 55 -HWE09120 GB4. Transformer Box (PUHY-P72, P96, P120, P144YJMU-A)Transformer(T03)Transformer(T02)

Strany 297

[ III Outdoor Unit Components ]- 56 -HWE09120 GB[3] Outdoor Unit Circuit Board1. Outdoor unit control boardCN332 Output 18VDC GND (Fan boar

Strany 298

[ III Outdoor Unit Components ] - 57 -HWE09120 GB2. M-NET board Power supply output for centralized control system (30VDC)

Strany 299

[ III Outdoor Unit Components ]- 58 -HWE09120 GB3. INV board(1) PUHY-P72TJMU-AFaston terminals have a locking function. Make sure the cable heads are

Strany 300

[ III Outdoor Unit Components ] - 59 -HWE09120 GB(2) PUHY-P96, P120, P144TJMU-AFaston terminals have a locking function. Make sure the cable heads a

Strany 301

[ III Outdoor Unit Components ]- 60 -HWE09120 GB(3) PUHY-P72, P96, P120, P144YJMU-A1) Before inspecting the inside of the control box, turn off th

Strany 302 - Error history

viHWE09120 GBBefore the test runCAUTIONTurn on the unit at least 12 hours before the test run.Keep the unit turned on throughout the season. If the un

Strany 303

[ III Outdoor Unit Components ] - 61 -HWE09120 GB4. Fan board(1) PUHY-P72, P96, P120, P144TJMU-ACNVDC Bus voltage input  N  P F01 Fuse 250VAC 15A LED

Strany 304

[ III Outdoor Unit Components ]- 62 -HWE09120 GB(2) PUHY-P72, P96, P120, P144YJMU-ACNVDCBus voltage input N PCNINVInverter output W V

Strany 305

[ III Outdoor Unit Components ] - 63 -HWE09120 GB5. Noise Filter(1) PUHY-P72TJMU-A GroundingTB21Input/output(L1)CN02Output L1 L2TB22Input/output(L2)T

Strany 306

[ III Outdoor Unit Components ]- 64 -HWE09120 GB(2) PUHY-P96, P120, P144TJMU-A GroundingF3 Fuse 250VAC 6.3A R1,2 Rush current protection resistor TB

Strany 307

[ III Outdoor Unit Components ] - 65 -HWE09120 GB(3) PUHY-P72, P96, P120, P144YJMU-ACN4Output(Rectified L2-L3 current) P NCN5Output(Rectified

Strany 308

- 66 -[ III Outdoor Unit Components ]GBHWE09120

Strany 309 - Data on indoor unit system

- 67 -HWE09120 GBIV Remote Controller[1] Functions and Specifications of MA and ME Remote Controllers ... 69[2] Group

Strany 311

[ IV Remote Controller ] - 69 -HWE09120 GBIV Remote Controller[1] Functions and Specifications of MA and ME Remote ControllersThere are two types of

Strany 312

[ IV Remote Controller ]- 70 -HWE09120 GB[2] Group Settings and Interlock Settings via the ME Remote Controller1. Group settings/interlock settings&

Strany 313

CONTENTSHWE09120 GBI Read Before Servicing[1] Read Before Servicing...

Strany 314

[ IV Remote Controller ] - 71 -HWE09120 GB<Entry found><No entries found>(C) To return to the normal displayWhen all the group settings a

Strany 315

[ IV Remote Controller ]- 72 -HWE09120 GB2. Remote controller function selection via the ME remote controller(A) To delete group settings(B) To dele

Strany 316 - Setting data

[ IV Remote Controller ] - 73 -HWE09120 GB1Hr.NOT AVAILABLEVENTILATIONSTAND BY DEFROSTTIMERCHECK[Operation Procedures]1. Press the [ON/OFF] button o

Strany 317

[ IV Remote Controller ]- 74 -HWE09120 GB[3] Interlock Settings via the MA Remote Controller1. LOSSNAY interlock setting (Make this setting only whe

Strany 318

[ IV Remote Controller ] - 75 -HWE09120 GB[4] Using the built-in Temperature Sensor on the Remote Controller1. Selecting the position of temperature

Strany 319

- 76 -[ IV Remote Controller ]GBHWE09120

Strany 320

- 77 -HWE09120 GBV Electrical Wiring Diagram[1] Electrical Wiring Diagram of the Outdoor Unit ...

Strany 322

[ V Electrical Wiring Diagram ] - 79 -HWE09120 GBV Electrical Wiring Diagram[1] Electrical Wiring Diagram of the Outdoor Unit1. Electrical wiring di

Strany 323

[ V Electrical Wiring Diagram ]- 80 -HWE09120 GB(2) PUHY-P96TJMU-ALED1:Normal operation(Lit)/Error(Blink)LED4:CPU inoperationON CN5Vyellow31OFFSW161F

Strany 324

HWE09120 GB

Strany 325

[ V Electrical Wiring Diagram ] - 81 -HWE09120 GB(3) PUHY-P120, P144TJMU-AContactorBoxCNVDC52F Fan motor 2(Heat exchanger) Fan motor 1(Heat exchang

Strany 326

[ V Electrical Wiring Diagram ]- 82 -HWE09120 GB(4) PUHY-P72, P96YJMU-A+-++++21+++++Transformer Box*1.Single-dotted lines indicate wiring not supplie

Strany 327

[ V Electrical Wiring Diagram ] - 83 -HWE09120 GB(5) PUHY-P120, P144YJMU-A+-++++21+++++ContactorBoxWVCN111black2875redwhite8 M3~U2CN1252FTSRblackwhit

Strany 328

[ V Electrical Wiring Diagram ]- 84 -HWE09120 GB[2] Electrical Wiring Diagram of Transmission BoosterAC208V/230VLRedRed RedWhiteGreen250V 2AGroundin

Strany 329

- 85 -HWE09120 GBVI Refrigerant Circuit[1] Refrigerant Circuit Diagram ...

Strany 331

[ VI Refrigerant Circuit ] - 87 -HWE09120 GBVI Refrigerant Ci rcuit[1] Refrigerant Circuit Diagram1. Outdoor unit(1) PUHY-P72, P96 models(2) PUHY-P1

Strany 332 - Other types of data

[ VI Refrigerant Circuit ]- 88 -HWE09120 GB[2] Principal Parts and Functions1. Outdoor unitPart nameSymbols (functions)Notes Usage Specifications Che

Strany 333

[ VI Refrigerant Circuit ] - 89 -HWE09120 GBThermis-torTH4(Discharge)1) Detects discharge air temper-ature2) Provides high-pressure pro-tectionDe

Strany 334 - Printed in Japan

[ VI Refrigerant Circuit ]- 90 -HWE09120 GBLinear expan-sion valveLEV1(SC control)Adjusts the amount of bypass flow from the liquid pipe on the outdo